Contact Directory Events Product Directory Company Background Cool It!Newsletter Master-Bilt Homepage Hot Links Literature Requests Service Spec sheets/CAD Energy Savers navagation bar

Endless Merchandisers

Service FAQs

Dealer/Service Locator

Master Controller Troubleshooting

Cabinet Troubleshooting

Warranty Guidelines

Installation/Operations Manuals

Recommended Wire Size & Length for Cabinets

Compressor Returns Policy

   
Service/Warranty Parts
Phone: 800-684-8988
Fax: 866-882-7629
Email: service@master-bilt.com
Parts Sales
Heritage Food Service Equipment
Phone:
800-458-5593 or 260-482-1444
Fax: 800-800-4981 or 260-482-4542
Email: master-biltinfo@hfse.com

Warranty &
Non-Warranty Parts Sales - Canada
Heritage Food Service Parts of Canada
Phone:
877-556-3646
Email: teamcanada@heritageparts.ca
 

 

Master Controller Troubleshooting

Master Controller issues include (alarm codes in parentheses):

1. Pressure transducer alarm (SP, PRSR)
2. Outlet sensor TS2 fails (So, SCSR)
3. Room sensor TS3 fails (SA, RMSR)
4. Low Superheat (LS, LOSH)
5. High room temperature (rH, HIRM)
6. Low room temperature (rL, LORM)
7. Defrost termination sensor TS1 fails (Sd, INSR)
8. Low pressure alarm (LP, PAL)
9. Communication alarm (CA, CMAL)
10. Electric expansion valve troubleshooting
11. Pressure transducer troubleshooting
12. Temperature sensor troubleshooting

 

1. Pressure transducer alarm (SP, PRSR)
Cause Solution

Bad transducer

Replace the pressure transducer

Out of range

Turn off power for a few seconds,  turn back on

Loose wire

Wire correctly
Wrong hook-up Wire correctly
Back to top
 
2. Outlet sensor TS2 fails (So, SCSR)
Cause Solution
Mechanical damage Replace sensor
Connection wire loose Tighten the connection wires on the controller terminal
Overheated Allow sensor time to cool down and check again. If no response, replace sensor.
Out of range Turn off power for a few seconds then turn back on

Back to top

 
3. Room sensor TS3 fails (SA, RMSR)
Cause Solution
Mechanical damage Replace sensor
Connection wire loose Tighten the connection wires on the controller terminal
Overheated Allow sensor time to cool down and check again. If no response, replace sensor.
Out of range Turn off power for a few seconds then turn back on

Back to top

 
4. Low superheat
Cause Solution
Superheat setting too low Change to correct setpoint (see manual)
Wrong location of TS2 Re-locate the outlet temperature sensor to the proper location (see manual)
Sensors loose Make sure the outlet sensor is properly insulated
Uneven feeding of coil circuits Make sure the distributor is feeding each circuit evenly
Refrigerant overcharge Use correct refrigerant charge
Defective electric expansion valve (EEV) Replace valve
Compressor stopped Check compressor

Back to top

 
5. High room temperature (rH, HIRM)
Cause Solution
Insufficient refrigeration Check system design to select a sufficient system
Heat load too large Call factory at 800-684-8988 for sizing recommendations

Compressor failed or high pressure has cut out

Re-set pressure control, clean condenser coil or replace failed compressor

Evaporator fans not running

Make sure fan relay on control board is closing

Walk-in door open too long

Make sure door is closed

Coil iced up

Check for possible air leak through walk-in walls

Back to top
   
6. Low room temperature (rL, LORM)
Cause Solution
Improper low temp setpoint

Change setpoint

Over-designed system Call factory at 800-684-8988 for sizing recommendations

Back to top

 
7. Defrost termination sensor TS1 fails (Sd, INSR)
Cause Solution
Mechanical damage          Replace sensor
Loose connection wire Tighten the connection wires on the controller terminal
Overheated Allow sensor time to cool down and check again. If no response, replace sensor.
Out of range Turn off power for a few seconds then turn back on
Back to top
 
8. Low pressure alarm (LP, PAL)
Cause Solution
Refrigerant leak Fix leak
Bad pressure transducer Replace transducer
Back to top
   
9. Communication alarm (CA, CMAL)
Cause Solution
Loose RS-485 connection Tighten terminals
Failed communications port

Improper setpoint in the Cn parameter

Replace controller board

Verify setpoints are correct for application (see manual)

Back to top
   
10. Electronic expansion valve troubleshooting

If the valve stops moving, depending upon how far open it is, one or more alarms may be displayed. These alarms include a low superheat alarm, a low temperature alarm and/or a high temperature alarm.

Use the following steps to troubleshoot the valve:

  1. Disconnect the valve from the controller

  2. The resistance between the black and white leads should be 90 ohms. The resistance between the black and red leads should be an open.

  3. The resistance between the red and green leads should be 90 ohms. The resistance between the white and green leads should be an open.

  4. The resistance between each lead and the brass housing of the valve should be an open.

  5. Read the AC, not DC, voltage across the black and white leads while the valve is moving. The AC voltage should be 11 to 13 VAC. The voltage will be close to 0 VAC when the valve is not moving.

  6. Repeat step 5 across the red and green leads.

If any voltage is out of tolerance, replace the controller. If the above steps pass, inspect for contamination in the valve or nicks on the seat of the valve.

CAUTION: If the valve was taken apart and was left running while taken apart, the piston may have come too far out of the motor assembly. If you reassemble the valve with the piston in this position, the threads in the piston will be stripped when the piston is forced into the seat while tightening the lock nut. Make sure the piston is drawn up far enough into the motor assembly before reassembling.

Back to top
 

11. Pressure transducer troubleshooting
Use the voltage chart below to determine if there is a fault with the pressure transducer.

Your Master Controller will be equipped with one of two types of pressure transducer (PT). The difference is in the color of sensor wires as noted below:

Current PT
(part number
19-14226 or 19-14223)

Previous PT
(part number
19-13955 or 19-14092)

Description

Red Black +VDC (+5)
Green White Signal (1+)
Black Green Ground (1-)

The GROUND is connected to terminal ‘1-‘ on the board. The SIGNAL lead is connected to terminal ‘1S’ on the board. The +VDC lead is connected to terminal ‘1+’ on the board. The chart below shows the characteristics of the pressure transducer. NOTE: The pressure transducer cannot be repaired but replaced only.

Pressure Sensor Simulation Values (0 to 150 PSIA)

BAR

PSIA

PSIG

V (Signal to Ground)
0 0 -14.6 0.509
0.69 10 -4.6 0.784
1.379 20 5.4 1.058
2.069 30 15.4 1.332
2.758 40 25.4 1.587
3.448 50 35.4 1.862
4.137 60 45.4 2.136
4.827 70 55.4 2.391
5.516 80 65.4 2.665
6.206 90 75.4 2.920
6.895 100 85.4 3.194
7.585 110 95.4 3.469
8.274 120 105.4 3.724

Back to top
 

12. Temperature sensor troubleshooting

Procedures to check temperature sensor tolerance with ice water:
 
  1. Use a cup of water with well-stirred ice. The water temperature should be an even 32°F.
  2. Submerge the room temperature sensor (TS3) into the water while the Master Controller is normally operating. Check the display for the value. If the sensor shows 32°F, it is working properly.
  3. Push PB1 and PB2 simultaneously until the green LED is blinking, scroll down the display to “in”, the defrost termination sensor (TS1) value. Submerge the sensor into the water. Check the display for the value. If the sensor shows 32°F, it is working properly.
  4. Scroll down the display to “oU”, the outlet sensor (TS2) value.
  5. Submerge the outlet sensor into the water. Check the display for the value. Again, if the sensor shows 32°F, it is working properly.
     
Compare the temperature and resistance to the chart below.

Temperature/Resistance Characteristics (-50 to 80 oF)

Temp. oF

Temp. oC

ohms*1k

 

Temp. oF

Temp. oC

ohms*1k

-50

-45.6

43.45

 

15

-9.4

7.579

-40

-40.0

32.31

 

20

-6.7

6.731

-35

-37.2

27.96

 

25

-3.9

5.993

-30

-34.4

24.27

 

30

-1.1

5.349

-25

-31.7

21.13

 

32

0

5.123

-20

-28.9

18.43

 

35

1.7

4.781

-15

-26.1

16.12

 

40

4.4

4.281

-10

-23.3

14.13

 

50

10.0

3.454

-5

-20.6

12.42

 

60

15.6

2.805

0

-17.8

10.94

 

70

21.1

2.294

5

-15.0

9.651

 

80

26.7

1.888

10

-12.2

8.544

 

 

 

 

Note: Use resistance at 32°F for sensor checking.

Back to top



A Standex International Corporation Company · ©2011, Master-Bilt, All Rights Reserved